MCC Formed Systems
| MCC FORM 3B SYSTEMS
Separation of busbars and functional units, as well as the separation of functional units within themselves. In addition, the external conductor terminals must be separated from the functional units, but the external conductor connection points do not need to be separated among themselves. External conductor connection points must be in a separate compartment.
Form 3B : The supply terminals of the functional units and the external conductor terminals are separated from each other.
MCC FORM 4B SYSTEMS
Separation of busbars and functional units, as well as the separation of functional units within themselves. In addition, external conductor terminals must also be separated from functional units, and external conductor connection points must be separated among themselves. External conductor connection points must be in a separate compartment.
Form 4B : The supply terminals of the functional units and the external conductor terminals are separated from each other. External conductor terminals are separated among themselves.
|
|
|